TX-6010-01-1 - Interlogix Wireless Heat & Smoke Detector

TX-6010-01-1 - Interlogix Wireless Heat & Smoke Detector
TX-6010-01-1 - Interlogix Wireless Heat & Smoke Detector
Item# TX-6010-01-1
List Price: $113.40
Your Price: $75.60

TX-6010-01-1 GE Wireless Heat & Smoke Detector Product Description:
This wireless sensor detects smoke and rising heat conditions. Unlike stand-alone smoke detectors (which only make a local alarm), this wireless smoke detector will sound and communicate with GeoArm's central station. In the event of an emergency, our professional operators will follow protocol and dispatch your local fire department if needed.

TX-6010-01-1 GE Wireless Heat & Smoke Detector Free Custom Programming:
Custom security system programming is FREE for all GeoArm monitored clients.

TX-6010-01-1 GE Wireless Heat & Smoke Detector GeoArm Recommendation:
Place smoke detectors inside all bedrooms and outside bedroom entrances. For multi-level homes make sure to have at least one smoke detector on each floor. Mount them high on ceilings at least 4" from any wall and when wall mounting at least 4" from the ceiling. To prevent false alarms, do not place a wireless smoke detector near a kitchen or stove and avoid damp or humid areas such as a bathroom or dusty areas such as a workshop or garage.

TX-6010-01-1 GE Wireless Heat & Smoke Detector Features:


TX-6010-01-1 GE Wireless Heat & Smoke Detector

Specifications
Dimensions (Diameter x Depth) Alarm: 14.2 x 6.1 (cm), 5.6 x 2.4 (in)
Base: 13.7 x 1.17 (cm), 5.4 x 0.46 (in)
Weight
Battery (1) CR123, 3V lithium batteries (included)
Battery Life
Operating Environment 40° to 100°F (4.4° to 37.8°C)
Approvals FCC, UL217, C-UL, US, CSFM
Voltage 3VDC
Typical Average Standby Current 35ľA
Typical Test Current 2mA
Typical Alarm Current 70mA
Low Battery Threshold 2.70V causes low battery signal
Sounder 85dBa at 10ft temporal pattern
Low Battery Beep Rate 1 every 45sec
Sensitivity 2.2% ± 1.3%/ft
Operating Humidity Range 0 to 95%, non-condensing
Color white
Drift Compensation Adjustment 0.5%/ft max
Heat Detectors Specifications Rate-of-rise: 15°/min>105°F (8.3°/min>40.6°C)
Fixed: 135°F ± 5°F (57.2°C ± 2.8 °C)
RFI Immunity 20V/m minimum; 0-1000MHz
RF Frequency 319.5MHz
Transmitter ID Pre-programmed, 1 Million codes
Modulation Type AM
Signal Format PWM
Signal Output Types alarm, tamper, test, low battery, trouble, supervisory