TX-6010-01-1 - GE Wireless Heat & Smoke Detector

TX-6010-01-1 GE Wireless Heat & Smoke Detector
TX-6010-01-1 GE Wireless Heat & Smoke Detector Product Description:
This wireless sensor detects smoke and rising heat conditions. Unlike stand-alone smoke detectors (which only make a local alarm), this wireless smoke detector will sound and communicate with GeoArm's central station. In the event of an emergency, our professional operators will follow protocol and dispatch your local fire department if needed.
TX-6010-01-1 GE Wireless Heat & Smoke Detector Free Custom Programming:
Custom security system programming is FREE for all GeoArm monitored clients.
TX-6010-01-1 GE Wireless Heat & Smoke Detector GeoArm Recommendation:
Place smoke detectors inside all bedrooms and outside bedroom entrances. For multi-level homes make sure to have at least one smoke detector on each floor. Mount them high on ceilings at least 4" from any wall and when wall mounting at least 4" from the ceiling. To prevent false alarms, do not place a wireless smoke detector near a kitchen or stove and avoid damp or humid areas such as a bathroom or dusty areas such as a workshop or garage.
TX-6010-01-1 GE Wireless Heat & Smoke Detector Features:
TX-6010-01-1 GE Wireless Heat & Smoke Detector
| Specifications |
| Dimensions (Diameter x Depth) |
Alarm: 14.2 x 6.1 (cm), 5.6 x 2.4 (in) Base: 13.7 x 1.17 (cm), 5.4 x 0.46 (in) |
| Weight |
|
| Battery |
(1) CR123, 3V lithium batteries (included) |
| Battery Life |
|
| Operating Environment |
40° to 100°F (4.4° to 37.8°C) |
| Approvals |
FCC, UL217, C-UL, US, CSFM |
| Voltage |
3VDC |
| Typical Average Standby Current |
35ľA |
| Typical Test Current |
2mA |
| Typical Alarm Current |
70mA |
| Low Battery Threshold |
2.70V causes low battery signal |
| Sounder |
85dBa at 10ft temporal pattern |
| Low Battery Beep Rate |
1 every 45sec |
| Sensitivity |
2.2% ± 1.3%/ft |
| Operating Humidity Range |
0 to 95%, non-condensing |
| Color |
white |
| Drift Compensation Adjustment |
0.5%/ft max |
| Heat Detectors Specifications |
Rate-of-rise: 15°/min>105°F (8.3°/min>40.6°C) Fixed: 135°F ± 5°F (57.2°C ± 2.8 °C) |
| RFI Immunity |
20V/m minimum; 0-1000MHz |
| RF Frequency |
319.5MHz |
| Transmitter ID |
Pre-programmed, 1 Million codes |
| Modulation Type |
AM |
| Signal Format |
PWM |
| Signal Output Types |
alarm, tamper, test, low battery, trouble, supervisory |