CO1224T Honeywell Carbon Monoxide Detector Product Description:
The Honeywell CO1224T four (4) wire carbon monoxide detector use a highly accurate and reliable electrochemical sensing cell to provide early warning of dangerous CO levels.
With RealTest™ Technology
The CO gas sensing cell used in the CO1224T carbon monoxide detector can be tested using a CO gas agent, fully meeting the requirements of NFPA 720: 2009. Simply put the detector into RealTest mode, spray a small amount of CO into the detector per the installation instructions, and within seconds the detector will alarm, indicating successful gas entry.
When dangerous amounts of CO are detected, the CO1224T carbon monoxide detector alert residents by sounding and flashing a temp 4 signal alarm. With 24/7 GeoArm central station monitoring, residents are guaranteed protection whether they are away from home, sleeping, or already suffering from the effects of CO.
The CO1224T carbon monoxide detector is designed for system operation. This carbon monoxide detector is fully listed to UL 2075 and offer a code-required trouble relay to send a sensor failure or end-of-life signal to the control panel and GeoArm's nationwide central monitoring station. The CO1224T also uses SEMS-type terminal Philips head screws for quicker and more positive wiring connections and code-requiring wiring supervision. With a low current draw, this carbon monoxide detector enables more devices to be connected to the alarm control panel, limiting the need to purchase extra power supplies or more expensive replacement panels. As 12/24VDC detectors, the CO1224T will operate on most existing security and fire alarm control panels.
CO1224T Honeywell Carbon Monoxide Detector Features:
- RealTest™ enables a functional test using canned CO
- Full compliance with UL 2075
- A code-required trouble relay
- Wiring supervision with SEMS terminals
- A six-year end-of-life timer
- 12/24 VDC
- A low current draw of 20mA in standby and 40mA in alarm
- Versatile mounting for wall and ceiling
- Accurate and reliable electrochemical sensing technology
- Optional CO-PLATE CO Detector Replacement Plate to upgrade previously installed competitor detectors
CO1224T Honeywell Photoelectric Smoke Detector
| Specifications |
| Dimensions (L x W x H) |
5.1 x 3.3 x 1.3 (in) |
| Sounder |
85db in alarm |
| Wiring |
4-wire |
| Operating Voltage |
12/24 VDC |
| Alarm Current |
40mA (75mA test) |
| Standby Current |
20mA |
| Alarm Contact Ratings |
0.5A at 30VDC |
| Operating Temperature Range |
32° to 104°F (0° to 40°C) |
| Humidity Range |
22 to 90% RH |
| Mounting |
Single-gang back box; Surface mount to wall or ceiling |
| Weight |
7oz. |
| Approvals |
ETL, FM, MEA, MSFM, UL |
| Do-It-Yourself with GeoArm
Save Your Money, Property and Life Today! |  |